5.4 Installation of Gas Damper
5.4.1 Before installation of gas dampers,the following contents shall be checked:
1 The closing of damper plate shall be flexible and reliable with normal operation;
2 The sealing contact surface of damper plate shall be smooth without distortion;
3 The wear-resisting lining and wear-resisting protection layer of gas dampers shall be out of cracks and breaking-off;
4 The damper installation direction and position indication are correct.
5.4.2 The installation of electric actuator of gas damper shall be in accordance with the following requirements:
1 The driving elements of electric actuators and regulating mechanism shall be flexible and reliable;
2 Carry out operation test to electric actuators,the operation direction and position indication shall be matched with the regulating mechanism and can meet the operating requirements;
3 When the valve actuator direction is not stated in the design documentation,the installation direction of valve operation system and actuators shall be convenient for operating and maintenance.