上QQ阅读APP看本书,新人免费读10天
设备和账号都新为新人
16 Installation of Cable Bearer and Tray
16.1 Dominant Items
16.1.1 The metal cable tray and bearer and the metal cable duct for leading in and out cable must be connected to earth(PE)or neutral(PEN)in accordance with the following requirements:
1 Metal cable tray and bearer shall have 2 points connected to PE or PEN main line.
2 The ends of connecting plate between non-galvanized metal cable trays shall be bridged to cooper-core ground wire,of which the minimum cross-section area shall be 4mm2.
3 The ends of connecting plate between galvanized cable trays shall not be bridged to ground wire but shall be provided with at least 2 fixing bolts with lock nuts or lock washers.